EXPERIMENTAL INVESTIGATION AND NUMERICAL MODELING OF THERMAL PERFORMANCE OF FIN-TUBE EVAPORATOR UNDER FROSTING CONDITIONS
Küçük Resim Yok
Tarih
2014
Dergi Başlığı
Dergi ISSN
Cilt Başlığı
Yayıncı
Turkish Soc Thermal Sciences Technology
Erişim Hakkı
info:eu-repo/semantics/closedAccess
Özet
Formation of frost in a heat exchanger reduces air passage area and lowers the performance of the heat exchanger due to the insulation effects it possesses. In this study, the performance of finned tube evaporator at transient regime was investigated both experimentally and numerically. When the experimentally obtained values of the evaporator's the total conductivity (UA) are compared with those obtained from the numerical model, it is found that they are very close to one another. On the numerical model, the effects of inlet air temperature, relative humidity and air velocity on evaporator's total conductivity (UA), air side pressure drop (Delta P-a) and frost thickness (delta(fst)), were respectively, studied. The results obtained from the numerical model show that Delta P-a and delta(fst) values increase with increasing air temperature and relative humidity while decreasing UA values.
Açıklama
Anahtar Kelimeler
Finned Tube, Evaporator, Heat Transfer, Frosting, Transient State
Kaynak
Isi Bilimi Ve Teknigi Dergisi-Journal Of Thermal Science And Technology
WoS Q Değeri
Q4
Scopus Q Değeri
Q4
Cilt
34
Sayı
2