EXPERIMENTAL INVESTIGATION AND NUMERICAL MODELING OF THERMAL PERFORMANCE OF FIN-TUBE EVAPORATOR UNDER FROSTING CONDITIONS

Küçük Resim Yok

Tarih

2014

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Yayıncı

Turkish Soc Thermal Sciences Technology

Erişim Hakkı

info:eu-repo/semantics/closedAccess

Özet

Formation of frost in a heat exchanger reduces air passage area and lowers the performance of the heat exchanger due to the insulation effects it possesses. In this study, the performance of finned tube evaporator at transient regime was investigated both experimentally and numerically. When the experimentally obtained values of the evaporator's the total conductivity (UA) are compared with those obtained from the numerical model, it is found that they are very close to one another. On the numerical model, the effects of inlet air temperature, relative humidity and air velocity on evaporator's total conductivity (UA), air side pressure drop (Delta P-a) and frost thickness (delta(fst)), were respectively, studied. The results obtained from the numerical model show that Delta P-a and delta(fst) values increase with increasing air temperature and relative humidity while decreasing UA values.

Açıklama

Anahtar Kelimeler

Finned Tube, Evaporator, Heat Transfer, Frosting, Transient State

Kaynak

Isi Bilimi Ve Teknigi Dergisi-Journal Of Thermal Science And Technology

WoS Q Değeri

Q4

Scopus Q Değeri

Q4

Cilt

34

Sayı

2

Künye