Performance optimization and improvement of dust laden air by dynamic control method for jet pulsed filters
Küçük Resim Yok
Tarih
2019
Yazarlar
Dergi Başlığı
Dergi ISSN
Cilt Başlığı
Yayıncı
Elsevier Science Bv
Erişim Hakkı
info:eu-repo/semantics/closedAccess
Özet
Almost all of the energy consumption of Jet Pulsed Filters is due to their reverse jet bag cleaning system. However, they have been working with simple bag cleaning algorithms. In order to optimize their energy consumption, these filters could be operated using an advanced automation with an innovative dynamic algorithms. In this study, initially, nine different types of novel cleaning algorithms were tested for Jet Pulsed Filters in an industrial plant by using an advanced automation system under real operating conditions. Then, an optimized cleaning algorithm was developed to operate all these filters efficiently, thanks to the data obtained from the experiments. By using the proposed algorithm instead of the classical one; energy consumption of the filter, the energy consumed per cubic meter of produced cleaning air and the waste oil generation were decreased by 50.7%, 73.9% and 86.5%, respectively. A 29.4 degrees C reduction in the temperature of the blower oil was also detected involving the extension of the oil life span by 7.4 times. Moreover, the average noise level in the factory was reduced from 83 dB to 79 dB. In this purpose, the number of bags cleaned per hour and the cleaning air production were increased by 183% and 89%, respectively. (C) 2019 The Society of Powder Technology Japan. Published by Elsevier B.V. and The Society of Powder Technology Japan. All rights reserved.
Açıklama
Anahtar Kelimeler
Automation, Clean-On-Time, Dust Collector, Energy Saving, Jet Pulsed Filters
Kaynak
Advanced Powder Technology
WoS Q Değeri
Q1
Scopus Q Değeri
Q1
Cilt
30
Sayı
7